Welcome to Digant Technologies, your partner for Telecom Automation & Monitoring Solutions!
Digant’s Integrated Intelligent Power Source Automation is used for switching the load automatically on to EB, Battery bank or DG based on the power source available at any given time and used for automating DG operations. The system monitors the grid supply, Telecom battery bank voltage, DG battery voltage and various alarms continuously, automatically starts and runs the DG set if the supply from the grid is not available and the battery bank voltage is lesser than pre configured threshold voltage. The system monitors and generates various alarms and makes efficient and optimal use of diesel generator in cases of non-availability of grid power.
EB on load
DG on load
Battery bank on load
DG Running Idle
Battery bank low voltage
DG battery low voltage
DG Freq out of range
LLOP
HWT
DG Fail to start
DG fail to stop
Parameter | Specification |
---|---|
Operating Voltage | 36VDC to 72VDC |
Telecom Battery bank monitor | Battery bank voltage measurement |
DG battery monitor | DG Low Battery voltage detection |
Power source automation | Auto / Manual mode |
Phase Selector modes | Single phase or two phase or 3 phase |
DG automation | Auto DG ON / OFF |
PFC alarm outputs (NO,COM,NC) | 12 Channel |
Configuration port | RS485 |
LED Indicators | Alarm outputs, EB and DG power source |
EB AC contactor | 25A, 40A, 60A, 80A |
DG AC contactor | 25A, 40A, 60A, 80A |
Load Current Supported | 25A, 40A, 60A, 80A |
SPD | Type 2 / class II |
Connectors for alarms output | Terminal block type |
Housing | IP63 |
Mounting | Outdoor |
Operating Temperature | -5°C to +60°C |
Humidity | 95% non-Condensing RH |
MCB-AC (ACDB Panel)
Rated current Rated voltage Rated Frequency Number of poles Rated short circuit breaking capacity Rated insulation voltage Rated impulse voltage |
6A ,16A,32A and 63A MCBs for each phase 240 / 415V AC 50Hz 1P (Single pole) 10kA 660V 6kV |
DG battery charger
Input Voltage Output voltage Float Mode DC Boost Mode Charging current in boost mode / float mode Output over voltage (Batt charger included) Output short circuit and overload Battery reverse polarity |
150-300 V AC 13.4 V DC 13.9 to 14 V DC 10 amps / 0 to 4 amps 15.5 V DC Continuously protected Protected latching mode |
Note : This product is available in four models
Integrated Intelligent Power Source Automation with 25A EB, DG contactors and MCBs, SPD,ACDB panel and DG battery charger – DTI2PSA1000
Integrated Intelligent Power Source Automation with 40A EB, DG contactors and MCBs, SPD,ACDB panel and DG battery charger – DTI2PSA1001
Integrated Intelligent Power Source Automation with 60A EB, DG contactors and MCBs,SPD, ACDB panel and DG battery charger – DTI2PSA1002